Zeta Alarm Systems Infinite 8 Manual de usuario Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 12
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
Premier M Plus 8-24 Zone Conventional Fire
Alarm Panel (PMP8, PMP16, PMP24)
The Premier M Plus control panels are designed
to full the requirements of EN54 parts 2 & 4
as well as being easy to install, operate and
maintain.
Being of modular construction, the basic M Plus panel
has 8 zone capacity, expandable to 16, 20 and 24 zones.
The Premier M Plus is suitable for surface mounting or
semi-ush tting (with just the door protruding).
Features
4 Common sounder circuits (150mA each)
Optional add-on zonal sounder circuits (50mA
Max.)
Serial repeater output
Auxiliary supply (29 Volts, 250mA)
Zone & sounder disablement facility
Sounder delay facility
Zonal to common timer (when tted with zonal
sounder boards)
One man test mode
Model PMP8 PMP16 PMP24
Part No. 37-020 37-022 37-024
Detection Zones 8 16 24
Mains Voltage 230V AC +10% / -15% @ 50/60 Hz
System Voltage 24V DC (nominal)
Zone Voltage 21V DC
Sounder Alarm Output 4 x 150mA @ 24V DC
Fault Relay Output 1 x relay SELV @ 1A maximum
Fire Relay Output 1 x relay SELV @ 1A maximum
Zone Capacity 32 Devices
Remote Sounder Activation N/A
Sounder Activation Delay 0 – 9 minutes in 1 minute increments
Zone End Of Line IN4002 Diode
Sounder End Of Line 10KΩ Resistor
Charger Voltage 28.4V DC (batteries disconnected)
Zone Short Circuit Protection 100mA
Charger Short Circuit Protection Batteries less than 20V
Charger Size 3.0 Amp
Operating Temperature 0°C - 50°C
Enclosure Size 485 x 477.5 x 125mm
0359-CPD-0143
2
Vista de pagina 1
1 2 3 4 5 6 7 ... 11 12

Comentarios a estos manuales

Sin comentarios