Zeta Alarm Systems Infinite 8 Manual de usuario Pagina 5

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 12
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 4
Fyreye MkII Conventional Detectors
(MKII-OP, MKII-OH, MKII-HF, MKII-HR)
The Fyreye MkII optical smoke detectors use a pulsing IR
LED & photodiode to detect IR scatter caused by smoke
entering the chamber.
The detector is particularly suitable for detecting
optically dense smoke, involving materials such as soft
furnishings, PVC, plastic, foam and all similar materials
which produce small visible particles (0.5 to 10μm).
The Fyreye Rate of Rise heat detectors (MKII-HR) use
a thermistor arrangement to sense a quick rise in
temperature and also a nal threshold temperature of
57°C. The Fyreye xed heat detector (MKII-HF) has a
single thermistor arrangement that gives an alarm at a
temperature of 90°C.
MKII-OP
MKII-HF
MKII-HR
MKII-OH
DIFT
Features
Designed to meet EN54 requirement
Lockable to base to stop unauthorised removal
Remote LED output
Compatible with all Fyreye bases
Model MKII-OP MKII-OH MKII-HF MKII-HR
Part No. 80-200 80-206 80-204 80-202
Detector Class Optical Smoke
Combined Smoke &
Heat
Fixed Heat Only
Rate of Rise & Fixed
Heat Detector
Design Standard EN54 part 7 EN54 parts 5 & 7 EN54 part 5 EN54 part 5
Approval DIFT
CPD Number 0845-CPD-232.1700 0845-CPD-232.1703 0845-CPD-232.1701 0845-CPD-232.1702
Operating Voltage 9-33V DC
Quiescent Current 40μA
Alarm Current @ 24V DC 34mA
Operating Temperature -10°C to +50°C
Minimum Continuous Temperature 0°C
Maximum Humidity 95% RH non-condensing
Alarm Condition 2.4% obscuration per metre
Fixed heat trigger
@90°C
Rate of rise or xed
heat trigger @ 57°C
Coverage 100m² 50m
2
IP Rating IP43
Start-up Time 10 Seconds
Size (with Base) 100 x 48 mm 101 x 64 mm 100 x 48 mm 100 x 48 mm
Weight (with Base) 75g (133g)
See table below for
CPD numbers
Model MKII-CB MKII-CB/D MKII-DB MKII-DB/D
Part No. 80-220 80-221 80-222 80-223
Type Common Base Common Base Diode Base Diode Base
Size 100 x 16mm 100 x 32mm 100 x 16mm 100 x 32mm
Weight 53g 64g 53.2g 64.2g
Bases
There are 4 types of mounting base available; standard or deep and with or without diode.
5
Vista de pagina 4
1 2 3 4 5 6 7 8 9 10 11 12

Comentarios a estos manuales