Innity 8 Conventional Fire Alarm Panel
(IN1, IN2, IN4, IN6, IN8)
The Innity 8 control panel is housed in the
most attractive, modern designed, ame
retardent ABS enclosure, utilising a switch
mode power supply. It has a fully removable
front cover which improves ease of access for
cable installations.
Optional Metal Backbox
The Innity 8 panel can also be ordered with a metal
back box facilitating upto 7ah batteries to t within the
panel housing. To order this version add “/M” to the end
of the model number (i.e. IN1/M, IN2/M, etc.)
Features
Access via password – removes problem of lost
keys
One man test facility
Disablement facility for zones & sounders
Space for up to 3Ah batteries
Sounder delay option
4 sounder circuits (IN4, IN6 & IN8)
Sounder circuits 3 and/or 4 can be congured as
Aux 24V supplies
Meets all requirements of latest EN54 part 2 and
part4
371mm
302mm
55
93
38
MODEL IN1 IN2 IN4 IN6 IN8
Part No 37-650 37-651 37-652 37-653 37-654
Mains Voltage 230V AC +10% / -15% @ 50/60 Hz
System Voltage 24V DC (Nominal)
Zone Voltage 21V DC (Nominal)
Sounder Alarm Output 2 x 150mA @ 24V DC 4 x 150mA @ 24V DC
Fault Relay 1 x Volt Free Relay, SELV @ 1A Max
Fault Relay 1 x Volt Free Relay, SELV @ 1A Max
Zone Capacity 32 devices per zone
Remote sounder operation Via N/O contact connected to Class Change
Sounder Activation Delay 0 to 10 minutes in 1 minute increments
Zone End of line 1N4002 Diode (Cathode Stripe to Zone +ve)
Sounder End of Line 10K resistor
Charger Voltage 27.6V
Battery cut off Battery voltage less than 20V
Battery Internal Resistance limit 0.9 ohm
Enclosure size 375 x 316 x 90 (mm)
Weight 3 kg (Excluding Batteries)
Maximum battery space 2 x 3.4 Ah, 12 Vdc sealed lead acid
0086-CPD-575041 KM-575040