INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624
Approved Document No: GLT-211-7-1
Issue 1.0 Author: MG Date: 22/1/2013 PAGE 14
7.3 Setting the device zone & ID (detectors, call points & sounders)
All devices will need to have their zone & ID switches set as described below. Switch 8 will depend on the type of the device.
Zone setting
Zone Number
Switch 5
Switch 6
Switch 7
1
ON
ON
ON
2
OFF
ON
ON
3
ON
OFF
ON
4
OFF
OFF
ON
5
ON
ON
OFF
6
OFF
ON
OFF
7
ON
OFF
OFF
8
OFF
OFF
OFF
Select the zone the device is fitted to (1 to 8). Each item on a zone has the same zone setting.
ID Setting
ID Number
Sw 1
Sw 2
Sw 3
Sw 4
ID Number
Sw 1
Sw 2
Sw 3
Sw 4
1
OFF
ON
ON
ON
9
OFF
ON
ON
OFF
2
ON
OFF
ON
ON
10
ON
OFF
ON
OFF
3
OFF
OFF
ON
ON
11
OFF
OFF
ON
OFF
4
ON
ON
OFF
ON
12
ON
ON
OFF
OFF
5
OFF
ON
OFF
ON
13
OFF
ON
OFF
OFF
6
ON
OFF
OFF
ON
14
ON
OFF
OFF
OFF
7
OFF
OFF
OFF
ON
15
OFF
OFF
OFF
OFF
8
ON
ON
ON
OFF
Give the device a unique zone ID number between 1 & 15. Each item on a zone has a different ID setting.
Settings for switch 8
Detector Type
Switch 8 Position
ID2 SOUNDER FLASHER BASE SMOKE DETECTOR
OFF
ID2 SOUNDER FLASHER BASE HEAT DETECTOR
ON
ID2 CALL POINT
ON
XTRATONE SOUNDER
ON
ZAIO-M ADDRESSABLE I/O INTERFACE
ON