11 OTHER CONNECTIONS
11.1 Repeater connection
The Infinity ID2 has an RS485 connection for a serial repeater. The repeaters has full control. Up to 3 repeater
can be powered from the Aux 24V DC output on the panel. If 4 or more are to be connected, then they must be
powered from external 24V power supplies. The panel supports up to 8 repeaters.