INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624
Approved Document No: GLT-211-7-1
Issue 1.0 Author: MG Date: 22/1/2013 PAGE 34
21. PCB TERMINATION CONNECTIONS.
Connection No
Description
Use
1- 8
Zone 1- 8
Connection for zone wiring
9
Sounder circuit 1
Connection of conventional sounders
10
Sounder circuit 2
Connection of conventional sounders
11
Fault Relay
Volt free relay. normally energised. Operates on any fault
12
Fire Relay
Volt free relay Operates on a fire condition
13
RS485
Connection for Repeater panel
14 &15
RS232
NOT ACTIVE
16
Aux Power Supply
Connects Loop 1 signals & general signals to display PCB
17
Battery Connections
Connects batteries to the PCB
18
Thermistor
Monitors battery temperature
19
24VDC Input
Connection from power supply