12.9 CHANGING INPUT/OUTPUT INTERFACE RESPONSE
12.9.1 DEFAULT SETTING
To change the DEFAULT interface response, select option 2 in the Alarm operation menu. From
here you will have the following options
Common
Zonal Detector
Zonal All
Own Input
Panel Link
Manual Alarm
Detector Alarm
Zonal MCP
These are the Triggers that will cause the I/O`s relay to operate
EG the option ZONAL DETECTOR would cause the I/O`s relay to operate if there is an alarm from a Detector in
it`s Zone.
12.9.2 SETTING INDIVIDUAL I/O UNIT OPERATION - RELAY
To alter the operation mode of an individual I/O unit, go to configuration menu 2
Select Edit Device.
Scroll to the required Address
Press button 8 (V) to cycle through the different Variations of I/O configuration
12.9.3 SETTING INDIVIDUAL I/O UNIT OPERATION - INPUT
To alter the INPUT mode of an individual I/O unit, go to configuration menu 2
Select Edit Device.
Scroll to the required Address
Press 6 (O) to cycle through the different Triggering Options of I/O configuration
The different options are:-
I/O signals general alarm when operated. Default setting. Used
when automatic & manual alarms are treated the same.
I/O signals a Detector alarm when operated. Used when device
being monitored is an automatic detector, and the system is set to
distinguish manual & automatic alarms.
I/O signals a MCP alarm when operated. Used when device being
monitored is Manually triggered, and the system is set to distinguish
manual & automatic alarms.
I/O signals a Pre-Alarm when operated. Used when a device being
monitored needs to give a warning signal , but not an alarm signal.
I/O signals a Fault Signal when operated. Used when a device being
monitored does not have a normally closed fault relay
I/O Zn-D A
Normal
Plant Room
Zone:01 ID:01
I/O Zn-D P
Normal
Plant Room
Zone:01 ID:01